NJ10-22-NGeneral specifications | ||
Switching element function | NAMUR, NC | |
Rated operating distance | 10 mm | |
Installation | non-flush | |
Output polarity | NAMUR | |
Assured operating distance | 0 ... 8.1 mm | |
Reduction factor rAl | 0.4 | |
Reduction factor rCu | 0.3 | |
Reduction factor r304 | 0.85 | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | |
Switching frequency | 0 ... 2000 Hz | |
Hysteresis | 1 ... 9 typ. 5 % | |
Current consumption | ||
Measuring plate not detected | min. 3 mA | |
Measuring plate detected | ≤ 1 mA | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR |
EN 60947-5-6:2000 IEC 60947-5-6:1999 |
|
Approvals and certificates | ||
FM approval | ||
Control drawing | 116-0165F | |
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | Products with a maximum operating voltage of ≤36 V do not bear a CCC marking because they do not require approval. | |
Ambient conditions | ||
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 2 m | |
Core cross-section | 0.75 mm2 | |
Housing material | PBT | |
Sensing face | PBT | |
Protection degree | IP68 | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 2G |