Supply
|
Connection
|
terminals 17, 18
|
Rated voltage
|
198 ... 253 V AC ; 45 ... 65 Hz
|
Power loss
|
2.5 W
|
Power consumption
|
approx. 3.2 VA
|
Input
|
Connection
|
terminals 1-, 2+; 8+, 9-
|
Rated values
|
acc. to EN 60947-5-6 (NAMUR), see system description for electrical data
|
Open circuit voltage/short-circuit current
|
approx. 8 V DC / approx. 8 mA
|
Switching point/switching hysteresis
|
1.2 ... 2.1 mA / approx. 0.2 mA
|
Pulse/Pause ratio
|
min. 0.5 ms / min. 0.5 ms
|
Line fault detection
|
breakage I ≤ 0.1 mA
|
Output
|
Connection
|
terminals 10, 11, 12; 13, 14, 15
|
Output
|
signal ; relay
|
Contact loading
|
253 V AC/2 A/500 VA/cos φ min. 0,7; 125 V AC/4 A/500 VA cos φ min. 0,7; 40 V DC/2 A/80 W ohmic load
|
Energized/De-energized delay
|
approx. 10 ms / approx. 20 ms
|
Mechanical life
|
107 switching cycles
|
Transfer characteristics
|
Switching frequency
|
< 10 Hz
|
Directive conformity
|
Electromagnetic compatibility
|
|
|
Directive 2004/108/EC
|
EN 61326-1:2006
|
Low voltage
|
|
|
Directive 2006/95/EC
|
EN 50178:1997
|
Conformity
|
Protection degree
|
IEC 60529
|
Ambient conditions
|
Ambient temperature
|
-25 ... 60 °C (-13 ... 140 °F)
|
Mechanical specifications
|
Protection degree
|
IP20
|
Mass
|
approx. 410 g
|
Dimensions
|
60 x 104 x 110 mm (2.4 x 4.1 x 4.3 in)
|
Data for application in connection with Ex-areas
|
EC-Type Examination Certificate
|
PTB 02 ATEX 2065 , for additional certificates see www.pepperl-fuchs.com
|
|
Group, category, type of protection
|
II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2]
|
Directive conformity
|
|
|
Directive 94/9/EC
|
EN 50014, EN 50020
|