General specifications | ||
Switching element function | NAMUR, NC | |
Rated operating distance | 1.5 mm | |
Installation | flush | |
Output polarity | NAMUR | |
Assured operating distance | 0 ... 1.215 mm | |
Reduction factor rAl | 0.4 | |
Reduction factor rCu | 0.3 | |
Reduction factor r304 | 0.85 | |
Nominal ratings | ||
Nominal voltage | 8 V | |
Switching frequency | 0 ... 2400 Hz | |
Hysteresis | typ. % | |
Current consumption | ||
Measuring plate not detected | min. 3 mA | |
Measuring plate detected | ≤ 1 mA | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR |
EN 60947-5-6:2000 IEC 60947-5-6:1999 |
|
Approvals and certificates | ||
FM approval | ||
Control drawing | 116-0165F | |
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
Ambient conditions | ||
Ambient temperature | -10 ... 60 °C (14 ... 140 °F) | |
Mechanical specifications | ||
Connection type | flexible leads PVC , 500 mm | |
Core cross-section | 0.14 mm2 | |
Housing material | brass, nickel-plated | |
Sensing face | PBT | |
Protection degree | IP67 | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G; 2G; 3G |